Single Core: Aluminium Wire Armoured (AWA)
MultiCore: Steel Wire Armoured (SWA)
Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Colour: Red or Black
2. Using features :Medium Voltage Power Cable Underground 11kv 15kv 33kv XLPE Power Cable
1. Rated voltage: Uo/U:3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
2. No. of core: Single-core or three cores.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. long-term is no more than 5 seconds). The highest temperature for a conductor is no more than 250ºC.
4. D.C. resistance of the conductor complies with the stipulations of 3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
5. The environment temperature should be no lower than 0oC when lay. Otherwise, it should be preheated.
6. The cable is laid without a horizontal drop limit.
7. Working Frequency Voltage Test: 3.5Uo/5min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.
9. Minimum Bending Radius: Single core - Fixed: 15 x overall diameter;3 core - Fixed: 12 x overall diameter
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)
Note: The single-core armored cables are used for the D.C. system only. If used for the A.C. system, the magnetic isolation should be applied to the steel armor wires of non-magnetical materials that should be used.
Size | Insulation Thickness | Copper Tape Insulation | Inner sheath Thickness | Steel wire diameter | Outer Sheath Thickness | ||
mm | mm | mm | mm | mm | |||
3 | × | 25 | 3.4 | 0.1 | 1.3 | 3.15 | 2.4 |
3 | × | 35 | 3.4 | 0.1 | 1.4 | 3.15 | 2.5 |
3 | × | 50 | 3.4 | 0.1 | 1.4 | 3.15 | 2.6 |
3 | × | 70 | 3.4 | 0.1 | 1.5 | 3.15 | 2.7 |
3 | × | 95 | 3.4 | 0.1 | 1.6 | 3.15 | 2.8 |
3 | × | 120 | 3.4 | 0.1 | 1.6 | 3.15 | 3 |
3 | × | 150 | 3.4 | 0.1 | 1.7 | 3.15 | 3.1 |
3 | × | 185 | 3.4 | 0.1 | 1.8 | 3.15 | 3.2 |
3 | × | 240 | 3.4 | 0.1 | 1.8 | 3.15 | 3.4 |
3 | × | 300 | 3.4 | 0.1 | 1.9 | 3.15 | 3.6 |
3 | × | 400 | 3.4 | 0.1 | 2.1 | 3.15 | 3.8 |
3 | × | 500 | 3.4 | 0.1 | 2.2 | 3.15 | 4.1 |