Type: | Insulated |
---|---|
Conductor Type: | Stranded |
Application: | Heating, Building |
Conductor Material: | Aluminum 8000 |
Sheath Material: | None |
Insulation Material: | XLPE |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Conductor (AWG or MCM) | Stranding | Insulation | Outside | Weight per 1000 ft. | Ampacity |
Thickness | Diameter | (AMPS) * | |||
(mls) | (in) | (lbs) | 90° C | ||
6 | 7/w | 45 | 0.26 | 39 | 60 |
4 | 7/w | 45 | 0.305 | 57 | 75 |
2 | 7/w | 45 | 0.36 | 84 | 100 |
1 | 19/w | 55 | 0.415 | 108 | 115 |
1/0 | 19/w | 55 | 0.45 | 132 | 135 |
2/0 | 19/w | 55 | 0.49 | 161 | 150 |
3/0 | 19/w | 55 | 0.54 | 198 | 175 |
4/0 | 19/w | 55 | 0.59 | 244 | 205 |
250 | 37/w | 65 | 0.655 | 292 | 230 |
300 | 37/w | 65 | 0.705 | 344 | 255 |
350 | 37/w | 65 | 0.75 | 396 | 280 |
400 | 37/w | 65 | 0.795 | 448 | 305 |
500 | 37/w | 65 | 0.87 | 550 | 350 |
600 | 61/w | 80 | 0.98 | 671 | 385 |
700 | 61/w | 80 | 1.04 | 774 | 420 |
750 | 61/w | 80 | 1.075 | 824 | 435 |
900 | 61/w | 80 | 1.161 | 0.979 | 480 |
1000 | 61/w | 80 | 1.23 | 1079 | 500 |
1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Two, Three or four conductors can be paralleled on a reel.
4. 90°C- XHHW-2 wet or dry locations.
5.Package:A-500' B-2,500' C-1,000' D-5,000'
UL Certificate for XHHW,SER,SEU,MC Cable
Suppliers with verified business licenses