Customization: | Available |
---|---|
Type: | Insulated |
Conductor Type: | Solid |
Still deciding? Get samples of US$ 0/Meter
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ASTM
CSA C22.2 No. 48 (non-metallic sheathed cable)
Canadian Electrical Code
Conductors:
Solid 14-10 AWG soft, uncoated copper, per ASTM-B3
Stranded 8 AWG conductor and larger uncoated, copper ASTM-B8
Insulation:
Color-coded Polyvinyl Chloride (PVC) compound meeting the required thickness of Type THHN with a heat-stabilized Nylon jacket rated for 90°C in dry locations.
Grounding Conductor:
Soft, uncoated copper per ASTM-B3 and/or ASTM-B8
Jacket:
A 30-mil, color-coded, PVC jacket is applied over the completed assembly as follows:
14 AWG White I 12 AWG Yellow I 10 AWG Orange I 8 AWG Black I 6 AWG Black
Size (AWG) | Number of Strands |
Ground Wire Size |
Insulation Thickness (in) |
Allowable Ampacity (Amps)* |
Outside Diameter (in) |
Approximate Net Weight (lbs/1000 ft) |
|
PVC | Nylon | ||||||
14/2 G | Solid | 14 | 0.015 | 0.004 | 15 | 0.170 x 0.390 | 56 |
12/2 G | Solid | 12 | 0.015 | 0.004 | 20 | 0.160 x 0.450 | 82 |
10/2 G | Solid | 10 | 0.020 | 0.004 | 30 | 0.210 x 0.493 | 123 |
8/2 G | 7 | 10 | 0.030 | 0.005 | 40 | 0.290 x 0.580 | 185 |
6/2 G | 7 | 10 | 0.030 | 0.005 | 55 | 0.330 x 0.695 | 256 |
14/3 G | Solid | 14 | 0.015 | 0.004 | 15 | 0.170 x 0.450 | 74 |
12/3 G | Solid | 12 | 0.015 | 0.004 | 20 | 0.345 | 107 |
10/3 G | Solid | 10 | 0.020 | 0.004 | 30 | 0.430 | 165 |
8/3 G | 7 | 10 | 0.030 | 0.005 | 40 | 0.555 | 251 |
6/3 G | 7 | 10 | 0.030 | 0.005 | 55 | 0.612 | 352 |
4/3 G | 7 | 8 | 0.040 | 0.006 | 70 | 0.820 | 565 |
2/3 G | 7 | 8 | 0.040 | 0.006 | 95 | 0.945 | 841 |
**14/4 G & 14/2-2 G | Solid | 14 | 0.015 | 0.004 | 12 | 0.345 | 90 |
**12/4 G & 12/2-2 G | Solid | 12 | 0.015 | 0.004 | 16 | 0.385 | 132 |
**10/4 G | Solid | 10 | 0.020 | 0.004 | 30 | 0.540 | 205 |