600V UL493 UF-B UNDERGROUND FEEDER AND BRANCH CABLE
Applications:
UF-B cable is generally used as a feeder to outside post lamps, pumps, and other loads or apparatus fed from a distribution point in an existing building as specified in the 2011 National Electrical Code. UF-B cable may be used underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. The voltage rating for the UF-B cable is 600 volts.
Standards:
Copper UF-B cable complies with the following:
• ASTM - B3 and B-8
• UL Standard 83
• UL Standard 493
• Federal Specification A-A-59544
• National Electrical Code, NFPA 70, 2011 Edition
• RoHS/ REACH
CONSTRUCTION:
Copper UF-B cable is manufactured as a 2 or 3 conductor cable, with or without a ground wire. Copper conductors are annealed (soft) copper, solid or compressed stranded. Phase conductors are polyvinyl chloride (PVC) insulated, nylon jacketed, color-coded for identification purposes. Jacketed with sunlight, moisture, and fungus-resistant gray PVC.
Conductor | Jacket Thickness (mils) | Ground Wire | Cable Dimension (mils) | |||
Size (AWG or kcmil) | No. of strands | Insulation and jacket thickness (mils) | ||||
Size (AWG) | No. of strands | |||||
TWO CONDUCTOR | ||||||
14 | 1 | 19 | 30 | 14 | 1 | 423X168 |
12 | 1 | 19 | 30 | 12 | 1 | 463X183 |
12 | 1 | 19 | 30 | Without Ground | 386X183 | |
10 | 1 | 24 | 30 | 10 | 1 | 518X215 |
8 | 7 | 35 | 45 | 10 | 1 | 678X302 |
6 | 7 | 35 | 45 | 10 | 1 | 770X338 |
THREE CONDUCTOR | ||||||
14 | 1 | 19 | 30 | 14 | 1 | 581X168 |
12 | 1 | 19 | 30 | 12 | 1 | 626X183 |
12 | 1 | 19 | 30 | Without Ground | 581X183 | |
10 | 1 | 24 | 30 | 10 | 1 | 727X215 |
8 | 7 | 35 | 45 | 10 | 1 | 1059X319 |
6 | 7 | 35 | 45 | 10 | 1 | 1223X361 |